GOOD FLOAT AND THERMOSTATIC STEAM TRAP TIME SERIES
VIEW
A float and thermostatic trap has two elements: the ball float and
the thermostatic bellows. Typically this trap will have a steady
modulating flow. This is caused by changes in the motion of the
float element as it adjusts to changes in the condensate level.
Occasionally the thermostatic element will contract to discharge
contaminants such as air. .
FLOAT AND THERMOSTATIC STEAM TRAP STUCK OPEN TIME SERIES
VIEW
When a "F&T" trap fails it can fail shut or open. If the ball
float becomes damaged due to an event such as water hammer, the
float will sink and shut the trap. In this instance there will be
no sound and the trap will be cold. If the valve is stuck open then
steam will rush through. This is an example of steam rushing
through.
Please wait for the sound image to open, then click on
the "play" icon in the middle of the screen.